ACI A/DLP-001-W-U-D-A-0 Differential Pressure Transmitter w/LCD Screen

ACI

MPN:
A/DLP-001-W-U-D-A-0
$182.49
$84.88
You save $97.61
SKU:
0006241-GSB
$182.49
$84.88
You save $97.61

Description

This is a NEW - unused 

Buyers and Re-sellers, don't miss this opportunity to purchase quality surplus equipment at a great price! There are many more surplus parts on our store, check it out!

Return Policy:

  • Returns are accepted within 60 days of the delivery date. Rest assured we will cover all return shipping costs!
  • All returns must be in "as shipped" original condition to qualify for a refund.
  • Photos of packing and product is required for damaged items.
  • Customer returns that satisfy all of the above requirements will be issued a refund including any applicable sales tax

Air Differential Pressure Transmitter, Multi-Range, ±0.5%, 0-1 WC, ±1 WC, 4-20 mA, 0-5 VDC, 0-10 VDC, Display


Accuracy

0.5%

Approvals

CE, Reach, RoHS2, WEEE

Direction

Uni-Directional, Bi-Directional

Measurement

Inches of Water Column

Media Compatibility

Liquid/Gas

Mount

Wall, DIN rail

Range

±1 in WC

Type

Multi

Display

LCD


Supply Voltage: 4-20 mA output; 16-36 VDC (250? load max.) / 22-36 VDC (500? load max.)

0-5 VDC / 0-10 VDC output; 16-36 VDC / 24 VAC (+/-10%)

Supply Current: 4-20 mA output; 24 mA minimum / 0-5 VDC / 0-10 VDC output; 6 mA max.)

Output Signals: Current output; 4-20 mA, 2-wire loop powered (standard); (Current limited to 21.4 mA max)

Voltage signals: 0-5 VDC/ 0-10 VDC Field selectable, 3-wire; output limited @ 5.25 & 10.5 VDC)

Response Time: (0-100% FSO) 8 seconds

Output Data Rate: 1 second

Pressure Ranges: Field Selectable Uni and Bi-directional Ranges

Accuracy: ± 0.5% FSO

Zero Function: Pushbutton Zero Function

Thermal Effects: +/-0.067% FSO /°C (0.12% FSO/°F)

Proof Pressure or Burst Pressure:

A/DPL-001, Proof: 270 inWC (67.2 kPa) / Burst: 415 inWC (103.3 kPa) for 1 inWC (249.8 Pa)

A/DPL-010, Proof: 350 inWC (87.12 kPa) / Burst: 550 inWC (139.9 kPa) for 10 inWC (2490.8 Pa)

A/DPL-040, Proof: 562 inWC (140 kPa) / Burst: 1004.7 inWC (250 kPa) for 40 inWC (9963.6 Pa)

Operating Temperature: -4 to 185°F (-20 to 85°C)

Compensated Temperature Range: 32 to 122°F (0 to 50°C)

Storage Temperature: -22 to 185°F (-30 to 85°C)

Operating Humidity: 10 to 95% RH, non-condensing

Media Types: Dry air or inert non-conductive gases

Enclosure Material: Flame Retardant Polycarbonate; UL94-5VA

Wiring Connections: Finger pushbutton (Spring) terminal blocks; accepts 16-24 AWG wires

Conduit Knockouts: Watertight Cordgrip Installed (1/2? NPT conduit fittings accepted when Cordgrip removed)

Pressure Fitting Material: Nickel Plated Brass or Stainless Steel

Tubing Size Accepted: 1/4" O.D. x 0.170" I.D. Poly Tubing

Dimensions: 4.25"L x 2.25"W x 6.125"H

Weight:

No Pitot Tube or Din Rail: Non-LCD Display Version: 0.53 lbs (0.240 Kg), LCD Display Version: 0.58 lbs (0.263 Kg)

With Pitot Tube & Din Rail:Non-LCD Display Version: 0.80 lbs (0.363 Kg), LCD Display Version: 0.85 lbs (0.385 Kg)

Approvals: CE, RoHS2, Reach, WEEE

Warranty: 5 years

Extra Information

Brand:
ACI
Weight:
0.06 LBS